High Resistance Pulse Grounding
High Resistance Pulse Grounding

Low-Voltage High-Resistance Grounding


Where continuity of service is a high priority, high-resistance grounding can add the safety of a grounded system while minimizing the risk of service interruptions due to grounds. The concept is a simple one: provide a path for ground current via a resistance that limits the current magnitude, and monitor to determine when an abnormal condition exists. This provides for maximum continuity of service, since no tripping occurs for the resistance limited ground fault. The ground current path is provided at the point where the service begins, by placing resistance in the connection from system neutral to ground. Control equipment continuously measures ground current; a relay detects when the current exceeds a predetermined level. An alarm alerts building personnel that a ground exists. The system has built-in fault tracing means to assist in finding the source of the ground. An integral transformer provides control power from the primary source.

Standard Features
. Current Sensing Ground Fault Detection (1-5 Amp Pickup / 0.5-20 Sec. Delay)
. Ground Current Transformer (10/10 Ratio)
. Control Circuit Disconnect Switch (Fused)
. Lockable Door Handle
. Ground Current Ammeter (0-10 Amps, 1% Accuracy)
. Indicating Lights
. Red (Ground Fault)
. Green (Normal)
. White (Pulse)
. Adjustable Pulsing Timer (0-10 Sec.)
. Tapped Resistors (1-5 Amps)
. 3-Position Selector Switch (Normal, Pulse, Test)
. Control Switch for Manual or Automatic Reset
. Ground Fault Contacts (1-NO/1-NC)
. Shorting Terminal Block for Ground Current Transformer
. UL Label
. Rated for use up to 200 kA Fault Current System
. Front Accessible
. Nylon Flag Type Wiremarkers
. Three "zig-zag" or "Wye-broken delta" grounding transformers for systems without a neutral point
600/347V (Maximum) WYE Systems

To add high-resistance grounding to a Wye-connected system, resistors are placed in series with the neutral-to-ground connection of the power source. The resistors are chosen to limit the current to a maximum value of 5 Amperes.

600V (Maximum) Delta Systems

To add high-resistance grounding to an ungrounded delta-connected system, a neutral point must be created. Three single-phase transformers can be interconnected in a zig-zag or Wye-broken delta configuration to provide such a neutral point. The transformers and grounding resistors are chosen to limit the ground current to a maximum value of 5 Amperes.

Ground Current Detection

Any time a system is energized, a small ground current called the "capacitive charging current" will be observed. For low-voltage (600V and below) systems, this naturally-occurring current is typically 1 Ampere or less. When one phase becomes grounded, additional current above the charging level will flow. As all ground current must flow through the grounding resistor/grounding transformer assembly, an ammeter in this circuit will read the total amount of ground current. By placing a current-sensing relay in series with the ammeter, the current relay can be adjusted to pick up at a level in excess of the capacitive charging current, thus indicating the abnormal condition. Alternatively, an optional voltmeter-relay can be connected across the grounding resistors. The voltage across the resistors is proportional to the amount of ground current. The voltmeter-relay's pickup adjustment is set above the capacitive charging current, to the desired detection level. In b oth current and voltage detection methods, the ground current ammeter provides a direct reading of the total, actual ground current present in the system at that time. It will be helpful to periodically note the ammeter's reading; a trend towards higher values may indicate the need for equipment maintenance and hence reduce the occurrence of unplanned shutdowns.

Indication and Alarm Circuits

When a fault is detected, an adjustable time delay is provided to override transients. When the time delay has been exceeded the green "normal" light will turn off, the red "ground fault" light will turn on, and the ground alarm contacts will transfer. If equipped with the optional alarm horn, it will sound. When the fault is cleared, the current/voltage relay will reset. If the reset control is set on "auto", the lights will return to "normal" on, "ground fault" off, and the ground alarm contacts will re-transfer. If the reset control is set on "manual", the lights and relay will remain latched until the operator turns the reset control to "reset". The lights and ground alarm contacts will then return to normal. The system can be reset only if the fault has been cleared. During a fault, the optional alarm horn can be silenced at any time by using the "alarm silence" pushbutton. It will not re-sound until either the system is reset, or the re-alarm timer expires. The re-alarm timer is activated by the "alarm silence" control. If the horn has been silenced but the fault has not been cleared, the timer will run. It has a range of 2-48 hours. When the timer times out, the horn will re-sound, alerting maintenance personnel that the fault has not been cleared.

Test Circuit

A test circuit Is provided to allow the user to quickly determine that the system is working properly. The test circuit will operate only under normal conditions - it will not allow testing if the system is sensing a fault. A separate grounding resistor is provided, connected to a relay operated by the "test" position of the mode selector switch. The relay's contact grounds phase B through the test resistor, causing ground current to flow. The system then reacts as it would under actual system ground conditions - lights transfer, alarm contacts transfer and the (optional) horn sounds.

Pulser Circuit

The pulser circuit offers a convenient means to locate the faulted feeder and trace the fault to its origin. The pulser is available any time a fault has been detected. The pulse intervals are controlled by an adjustable recycle timer. The "pulse" light flashes on and off, corresponding to the on-off cycles of the pulser contactor. The pulser contactor switches a bank of resistors on and off, thus allowing a momentary increase in the ground current (approximately a 5 Ampere current pulse above the ground current).

Locating a Ground Fault

The current pulses can be noted with a clamp-on ammeter when the ammeter is placed around the cables or conduit feeding the fault. The operator tests each conduit or set of cables until the pulsing current is noted. By moving the ammeter along the conduit, or checking the conduit periodically along its length, the fault can be traced to its origin. The fault may be located at the point where the pulsing current drops off or stops. If little or no change in the pulsing current is noted along the entire length of a conduit, then the fault may be in the connected load. If the load is a panelboard, distribution switchboard or motor control center, repeat the process of checking all outgoing cable groups and conduits to find the faulted feeder. If the fault is not found in an outgoing feeder, the fault may be internal to that equipment.

Application Notes

It may not be possible to precisely locate faults within a conduit. The ground current may divide into many components, depending on the number of cables per phase, number of conduits per feeder, and the number and resistance of each ground point along the conduits. The resulting currents may be too small to allow detection or may take a path that the ammeter cannot trace. An important note to keep in mind is that while the pulser can greatly aid in locating a fault, there may be certain conditions under which the pulses cannot be readily traced, and other test procedures (meg-ohm, high-potential, etc.) may be needed.

Sequence of Operations

Normal
Green "normal" light on.
Red "ground fault" light off.
White "pulse" light off.
System control switch in "normal" position.
Reset control switch in either "auto" or "manual".

Test
Turn and hold the system control switch in the "test position". Phase B will be grounded via the test resistor. The ground-current will activate the sensing circuit, causing the green "normal" light to turn off and the red "ground fault" light to turn on. The pulser will be activated as well. The white "pulse" light will turn on and off as the pulser contactor closes and opens. The ground current ammeter will display the total ground current, including the incremental pulse current. When ready, return the system control switch to "normal". The pulser will stop. If the reset control is in the "manual" position, turn it to "reset" to reset the fault sensing circuit. The red "ground fault" light will turn off, and the green "normal" light will turn on. Test mode is not available if the system is detecting a ground. The sensing circuit will disable the test circuit.

Ground Fault
When the sensing circuit detects a fault, the green "normal" light will turn off and the red "ground fault" light will turn on. The ground current ammeter will indicate the total ground current. To use the pulser, turn the system control switch to "pulse". The pulser contactor will cycle on and off as controlled by the recycle timer relay. Use the clamp-on ammeter to locate the faulted feeder. Open the feeder and clear the fault. If the reset control switch is in the "manual" position, turn it to "reset" to reset the sensing circuit. (If reset control is in "auto", it will reset itself.) When ready to restore service to the load, close the feeder. Return the system control to "normal."

Construction Features

. Tapped resistors supply ground current between 1 and 5 Amperes in 1 Ampere increments.
. Pulse current is an additional 5 Amperes. (Pulse currents of a lower magnitude may be difficult to detect.)
. Pulse timer is adjustable from 3 to 60 pulses per minute.
. Time delay for current sensing relay is 0.5 to 20 seconds with a 1 to 5 Ampere pick up. (Time delay for voltage sensing relay is 1 to 60 seconds.)
. Fused disconnects are supplied for control and ground transformers.
. All door mounted equipment is guarded against accidental contact.
. All exterior nameplates are fastened with stainless steel screws.
. Nameplates are 2-ply with 3 /16-inch lettering. The nameplate size is 1-inch x 2 1 /2inches White background with black lettering is standard.
. Top and bottom cable entry areas are standard.
. Phase and neutral terminals accept #12 AWG to #8 AWG.
. Ground terminal accepts wire sizes from #8 AWG to 500 kcmil. Ground bus is 1 /4- inch x 2 inches copper.
. The paint is applied using an electro-deposition coating system. Metal surfaces are prepared by spray and dip cleaning, and phosphatizing. The standard color is ANSI 61, light gray.
. Line side fuses are rated for use up to 200 kA fault current systems. All other fuses are rated to protect each circuit as required.
. The resistors are wire wound on a steel tube, insulated by Micarta. Resistors are mounted on a steel rack with ceramic insulators.
. No. 8 AWG wire is used for internal connections from the neutral point to ground. Control connections are a minimum of #14 gauge. All control wires insulation is type SIS.
. UL listed.
. A list of recommended spare parts can be provided after the final engineering is complete.
. Steel pocket on the inside of the door is provided to hold drawings and manuals.

Ratings

. Voltage rating shall be as indicated on the drawings. The entire assembly shall be suitable for 600 volts maximum AC service.
. The assembly shall be rated to withstand mechanical forces exerted during short-circuit conditions when connected directly to a power source having available fault current [of (30,000) (42,000) (50,000) (65,000) (85,000) (100,000) (200,000) amperes symmetrical at rated voltage] [as shown on the drawings].
. All ratings shall be tested to the requirements of ANSI C37.20.1 and UL witnessed and approved.

Construction

. The assembly shall consist of the required number of vertical sections bolted together to form a rigid assembly. The sides and rear shall be covered with removable bolt-on covers. All edges of front covers or hinged front panels shall be formed. Provide ventilators located on the roof of the switchgear to ensure adequate ventilation within the enclosure.
. The assembly shall be provided with adequate lifting means and shall be capable of being moved into installation position and bolted directly to [contractor supplied floor sills to be set level in concrete per manufacturer's recommendations] [the floor without the use of floor sills provided the floor is level to 1/8-inch per 3-foot distance in any direction]. Base of assembly shall be suitable for rolling directly on pipes without skids.
. The assembly shall be Cutler-Hammer C-HRG high-resistance grounding equipment utilizing Cutler-Hammer grounding resistors and/or grounding transformers as herein specified or approved equal.
. Each vertical steel unit forming part of the assembly shall be a self-contained housing having an instrument compartment and a resistor compartment. The control compartment shall be segregated from the resistor compartment by means of steel barriers or, if indicated on the drawings, the resistor assembly shall be a separately mounted component furnished in its own ventilated enclosure.
. The assembly shall be fully front accessible. Rear or side access shall not be required for installation or maintenance.

Bus

. A copper ground bus shall be firmly secured to the assembly. It shall be [silver-plated copper] [tin-plated copper]. Provide terminals for connection of the system grounding conductor, suitable for #8 AWG to 500 kcmil, copper or aluminum.

Wiring/Terminations

. Small wiring, necessary fuse blocks and terminal blocks within the switchgear shall be furnished as required.
. All control wire insulation shall be type SIS. Wire bundles shall be secured with nylon ties and anchored to the assembly without the use of adhesive-only wire anchors. All current transformer secondary leads shall first be connected to front accessible short-circuiting terminal blocks before connecting to any other device. Shorting screws with provisions for storage shall be provided. All groups of control wires shall be provided with terminal blocks with suitably numbered strips. Provide wire markers at each end of all control wiring.

Metering and Controls

 A. Provide a separate control compartment with front hinged door that includes the following:
. A switchboard type ground current ammeter, 1% accuracy, 250 degree scale, 0 to 10A AC.
. System control selector switch with PULSE/NORMAL/TEST positions. Switch shall spring-return from the test position.
. Reset control selector switch with AUTO/MANUAL/RESET positions. Switch shall spring-return from RESET position. The AUTO position shall cause the ground fault relay to automatically reset when a ground is no longer detected. The MANUAL position shall cause the ground alarm relay to latch and remain latched until the selector is moved to the RESET position by the operator.
. A green lamp to indicate that the system is in normal condition, a red lamp to indicate that a ground fault has been detected and a white lamp that flashes at the same rate and at the same time as the pulsing contactor.
. An instruction nameplate that provides the operator with a step-by-step procedure for operating the controls.
. A rating nameplate that states the maximum ground current, maximum pulse current and duty rating of the equipment at maximum current levels.
. A ground voltage meter-relay, 3% accuracy, 90 degree scale, 4-1/2-inch panel-type, AC voltage-scaled to coordinate with system voltage, UL component-recognized. [Setpoint adjustment shall be via a front-mounted knob.] [Meter-relay to be equipped with dual setpoints. One setpoint output contact set shall be wired to terminal blocks for field connection as shown on the drawings. Setpoint adjustments shall be via front-mounted knobs.]
. An alarm horn with an alarm silence pushbutton and re-alarm timer. The horn shall be a heavy-duty, high-decibel type, adjustable from 78 to 103 db. Alarm silence control shall reset when ground relay is reset. Alarm shall automatically re-sound at the end of a 2- to 48-hour field-settable time interval if alarm has been silenced but ground fault still exists. Re-alarm timer shall not be defeatable via any control device.
B. Provide the following control devices and features:
. One normally open and one normally closed ground fault alarm contact each rated 10 amps at 240 volts AC.
. Test loops (for convenient attachment of a snap-on hand-held ammeter) in the ground current and test current circuits.
. A test circuit protected by a current-limiting fuse rated 200,000 amps and operated by the system control switch via a panel-mounted test circuit relay. The test circuit shall connect phase B to ground through a current-limiting resistor. The test circuit shall not be direct-wired to the door-mounted test switch. The test circuit relay shall be constrained from operating if a ground fault is presently being detected.
. A pulsing contactor, controlled by an adjustable timer. The timer shall allow an adjustment range of 0 to 10 seconds.
. 120 Vac control power transformer for self-contained operation. The control power transformer shall have current limiting primary fuses rated 200,000 AIC at the system voltage.
. Primary disconnect switch-mounted ahead of test and control power fuses.
. Tapped resistors with taps wired out to a convenient front accessible terminal block. Taps shall provide 1 to 5 amperes of ground current in 1 amp increments. Resistors shall be heavy-duty industrial type, edgewound or wirewound design. Each resistor tube shall have a stamped steel rating nameplate. The resistor assembly shall be interconnected with 200 degree C rated #8 AWG wire. All connections to the resistor assembly shall be #8 AWG SIS wire.
. All wiring in the grounding circuit from the neutral point to the system ground terminal shall be #8 AWG type SIS minimum. All control wiring shall be #14 AWG type SIS minimum.
. A detailed schematic shall be furnished that accurately and completely describes the control and grounding circuits. All wire designations, terminal points, control device, and selector switch contact developments shall be shown. The schematic and the accompanying wiring diagrams shall be amended as required after final testing at the factory. An as-built copy of the schematic, wiring diagrams and material list shall be packed with the unit prior to shipment. Provide a drawing pocket secured by screws or weldment for drawing storage within the assembly.
. When the power system source has a neutral terminal, as indicated on the contract drawings, the grounding resistors shall be connected to that neutral. When the power system source has no neutral point, [Zig-Zag] [Wye-broken delta] transformers shall be furnished in the assembly to provide a neutral point.
Enclosures . NEMA 1 Freestanding Enclosure
. Outdoor Non Walk-in Enclosure . Assembly shall be enclosed in an outdoor NEMA 3R enclosure conforming to all applicable requirements of UL. The enclosure shall have a roof sloping toward the rear.
. The enclosure shall be provided with a front hinged door with provisions for padlocking. Ventilating openings shall be provided complete with removable air filters.

. NEMA 1 Wall Mounted Enclosure
. OEM Panel Mounted, No Enclosure

Nameplates

. Engraved nameplates, mounted on the face of the assembly, shall be furnished for all main and feeder circuits as indicated on the drawings. Nameplates shall be laminated plastic, black characters on white background, and secured with screws. Characters shall be 3/16-inch high, minimum.
. Control components mounted within the assembly, such as fuse blocks, relays, pushbuttons, switches, etc., shall be suitably marked for identification corresponding to appropriate designations on manufacturer's wiring diagrams.

Finish

. All exterior and interior steel surfaces of the switchgear shall be properly cleaned and provided with a rust-inhibiting phosphatized coating. Color and finish of the assembly shall be the manufacturer's standard.


Medium Voltage High-Resistance Pulsing Ground Systems (5 kV Max.)
Where continuity of service is a high priority, high-resistance grounding can add the safety of a grounded system while minimizing the risk of service interruptions due to grounds. The concept is a simple one: provide a path for ground current via a grounding transformer (with adjustable resistance across its secondary) that limits the current magnitude and a monitor to determine when an abnormal condition exists.
The ground current path is provided at the point where the service begins, by placing a predominantly resistive impedance in the connection from system neutral to ground. Control equipment continuously measures ground current; a relay detects when the current exceeds a predetermined level. An alarm alerts building personnel that a ground exists. The system has built-in fault tracing means to assist in finding the source of the ground. A 120-volt AC supply (remote) is required for control power for the system


Standard Features . Current sensing ground fault detection (2-10 amperes pickup/0.5-20 second delay)
. Ground current transformer (10/10 ratio)
. Control circuit pull fuseblock
. Ground current ammeter (0-10 amperes, 1% accuracy)
. Indicating lights

Red (ground fault)
Green (normal)
White (pulse)
. Adjustable pulsing timer (0-10 seconds)
. Tapped resistors (limits primary current to 3-6 amperes)
. 3-position selector switch (normal, pulse, test)
. Control switch for manual or automatic reset
. Ground fault contacts (1-NO/1-NC)
. Shorting terminal block for ground current CT
. UL label
. Wiremarkers

Product Standards
. Tapped resistors supply primary ground current between 3 and 6 amperes in 1 ampere increments.
. Pulse current is an additional 4 amperes. (Pulse currents of a lower magnitude may be difficult to detect.)
. Pulse timer is adjustable from 3 to 60 pulses per minute.
. Time delay for current sensing relay is 0.5 to 20 seconds with a 2 to 10 ampere pickup. Time delay for voltage sensing relay is 1 to 60 seconds.
. "Pull-type" fuse disconnects are supplied for control equipment protection.
. All exterior nameplates are fastened with stainless steel screws.
. Nameplates are 2-ply with 3/16-inch lettering. The nameplate size is 1-inch x 2-1/2-inch. White background with black lettering is standard.
. Top and bottom cable entry areas are standard.
. Phase and neutral terminals accept #4 AWG to 500 kcmil.
. Ground terminal accepts wire sizes from #4 AWG to 500 kcmil. Ground bus is 1/4-inch x 2-inch copper.
. The powder paint is applied to the parts electrostatically. Metal surfaces are prepared by spray cleaning and phosphatizing. The powder paint is a polyester urethane. The standard color is ANSI 61, light gray. The paint is applied to a thickness of 1.5 mil.
. Appropriate current limit drawout type fuses are provided. The chassis is mechanically interlocked with a secondary circuit breaker to prevent its withdrawal under load conditions.
. Resistors are grid type to provide the maximum area for heat dissipation.
. No. 4 AWG wire is used for internal connections from the neutral point to ground. Control connections are a minimum of #14 gauge. All control wires insulation is type SIS.
. UL listed.
. Recommended spare parts list.
. Steel pocket on the inside of the door is provided to hold drawings and manuals.

Note: The C-HRG units can be applied on any 3-wire distribution system, regardless of the manufacturer of the distribution equipment or source power transformer.
4200V (Maximum) Delta Systems
To add high-resistance grounding to an ungrounded delta-connected system, a neutral point must be created. Three single-phase transformers can be interconnected in a wye-broken delta configuration to provide such a neutral point. The transformers and grounding resistors are chosen to limit the ground current to a maximum value of 6 amperes.

Application Note: The neutral point may not be used to serve phase-to-neutral loads. Also, this technique may be applied on wye-connected sources when the neutral point is not conveniently accessible from the service entrance location. This method is shown in the illustration to the left. One delta high-resistance grounding would ground the 5 kV system.

4200V (Maximum) Wye Systems
To add high-resistance grounding to a wye-connected system, resistors are placed across the secondary of a grounding transformer whose primary is placed in series with the neutral-to-ground connection of the power source. The resistors are chosen to limit the current to a maximum value of 6 amperes.

Application Note:
Per 1993 NEC 250-5b, exception No. 5, line-to-neutral loads may not be connected to a system in which the neutral is resistance-grounded. Refer to the illustration on page M3-10. Because the system shown has two switchable sources not permanently connected to the bus, two wye-type grounding systems are required.

Ground Current Detection
Any time a system is energized, a small ground current called the "capacitive charging current" will be observed. For medium voltage (4200V and below) systems, this naturally occurring current is typically 3A or less. When one phase becomes grounded, additional current above the charging level will flow. As all ground current must flow through the grounding resistor/grounding transformer assembly, an ammeter in this circuit will read the total amount of ground current. By placing a current sensing relay in series with the ammeter, the current relay can be adjusted to pick up at a level in excess of the capacitive charging current, thus indicating the abnormal condition. Alternatively, an optional voltmeter-relay can be connected across the grounding resistors. The voltage across the resistors is proportional to the amount of ground current. The voltmeter-relay's pickup adjustment is set above the capacitive charging current, to the desired detection level. In bot h current and voltage detection methods, the ground current ammeter provides a direct reading of the total actual ground current present in the system at that time. It will be helpful to periodically note the ammeter's reading: a trend toward higher values may indicate the need for equipment maintenance, and hence reduce the occurrence of unplanned shutdowns.

Indication and Alarm Circuits
When a fault is detected, an adjustable time delay is provided to override transients. When the time delay has been exceeded, the green "normal" light will turn off, the red "ground fault" light will turn on, and the ground alarm contacts will transfer. If equipped with the optional alarm horn, it will sound. The grounding transformer secondary breaker must be closed for the system to be operational. Should this breaker be opened at any time, the system will signal a ground fault condition as a fail-safe feature. The breaker must be closed to clear the alarm signal. When the fault is cleared, the current/voltage relay will reset. If the reset control is set on "auto," the lights will return to "normal" on, "ground fault" off, and the ground alarm contacts will re-transfer. If the reset control is set on "manual," the lights and relay contacts will remain latched until the operator turns the reset control to "re set." The lights and ground alarm contacts will then return to normal. The system can be reset only if the fault has been cleared. During a fault, the optional alarm horn can be silenced at any time by using the "alarm silence" pushbutton. It will not re-sound until either the system is reset, or the re-alarm timer expires. The re-alarm timer is activated by the "alarm silence" control. If the horn has been silenced but the fault has not been cleared, the timer will run. It has arange of 2-48 hours. When the timer times out, the horn will re-sound, alerting maintenance personnel that the fault has not been cleared.

Test Circuit
A test circuit is provided to allow the user to quickly determine that the system is working properly. The test circuit will operate only under normal conditions - it will not allow testing if the system is sensing a fault. The test operation does not simulate an actual system ground fault. It does, however, test the complete controls of the fault indication and pulsing circuitry. The system then reacts as it would under actual system ground conditions - lights transfer, alarm contacts transfer and the (optional) horn sounds.

Pulser Circuit
The pulser circuit offers a convenient means to locate the faulted feeder and trace the fault to its origin. The pulser is available any time a fault has been detected. The pulse intervals are controlled by an adjustable recycle timer. The "pulse" light flashes on and off, corresponding to the on-off cycles of the pulser contactor. The pulser contactor switches a bank of resistors on and off, thus allowing a momentary increase in the ground current (approximately a 4A current pulse above the ground current).

Locating a Ground Fault
The current pulses can be noted with a clamp-on ammeter when the ammeter is placed around the cables or conduit feeding the fault. The operator tests each conduit or set of cables until the pulsing current is noted. By moving the ammeter along the conduit, or checking the conduit periodically along its length, the fault can be traced to its origin. The fault may be located at the point where the pulsing current drops off or stops.
If little or no change in the pulsing current is noted along the entire length of a conduit, then the fault may be in the connected load. If the load is a panelboard, distribution switchboard or motor control center, repeat the process of checking all outgoing cable groups and conduits to find the faulted feeder. If the fault is not found in an outgoing feeder, the fault may be internal to that equipment.

Application Note:
It may not be possible to precisely locate faults within a conduit. The ground current may divide into many components, depending on the number of cables per phase, number of conduits per feeder, and the number and resistance of each ground point along the conduits. The resulting currents may be too small to allow detection or may take a path that the ammeter cannot trace. An important note to keep in mind is that while the pulser can greatly aid in locating a fault, there may be certain conditions under which the pulses cannot be readily traced, and other test procedures (megohm, high-potential, etc.) may be needed.

Sequence of Operations
Normal
Green "normal" light on.
Red "ground fault" light off.
White "pulse" light off.
System control switch in "normal" position.
Reset control switch in either "auto" or "manual."

Test
Turn and hold the system control switch in the "test" position. This mode will test the control circuitry only. It will by-pass the sensing circuit and cause the green "normal" light to turn off and the red "ground fault" light to turn on. The pulser will be activated as well. The white "pulse" light will turn on and off as the pulser contactor closes and opens. However, the ground current ammeter will not display the total ground current, including the incremental pulse current. When ready, return the system control switch to "normal." The pulser will stop. If the reset control is in the "manual" position, turn it to "reset" to reset the fault sensing circuit. The red "ground fault" light will turn off, and the green "normal" light will turn on. Test mode is not available the system is detecting a ground. The sensing circuit will disable the test circuit.

Ground Fault
When the sensing circuit detects a fault, the green "normal" light will turn off and the red "ground fault" light will turn on. The ground current ammeter will indicate the total ground current. To use the pulser, turn the system control switch to "pulse." The pulser contactor will cycle on and off as controlled by the recycle timer relay. Use the clamp-on ammeter to locate the faulted feeder. Open the feeder and clear the fault. If the reset control switch is in the "manual" position, turn it to "reset" to reset the sensing circuit. (If reset control is in "auto," it will reset itself.) When ready to restore service to the load, close the feeder. Return the system control to "normal."

General
Provide a high-resistance grounding system as a means to provide a path for ground current via a resistance that limits the current magnitude. While monitoring the ground current, the system must be able to determine when an abnormal condition exists. Once the abnormality is detected, the system shall alert building personnel that a ground exists. The system shall be suitable for 5000 Volt maximum service, and designed and tested for that voltage class in accordance with the latest standards of NEMA and UL.

System Ratings and Features
Provide a UL-labeled high-resistance grounding system equal to Cutler-Hammer catalog number _________ for use on a system with a short circuit capacity of __kA at ____ Volts. The structure shall be a [free-standing NEMA 1] [free-standing NEMA 3R]. The system neutral point shall be provided by [the power transformer's wye neutral point] [wye-broken delta grounding transformers]. The ground current shall be detected with [an overcurrent relay] [a single-setpoint voltmeter relay]. [An alarm horn with re-alarm timer is required.] [An alarm to indicate the loss of control power is required.] The indicating lights shall be [transformer-type incandescent lamps] [push-to-test transformer type lamps]. Control wiring shall be marked using [wrap-on type] [heat-shrink sleeve type] wiremarkers. [A portable clamp on detector with 1/2/5/10/20 ampere scales, a shorting switch and a storage case is required].
In addition to the components specified above, the following shall be supplied with each system:

. Ground current transformer (10/10 ratio)
. Control circuit disconnect switch (fused)
. Ground current ammeter (0-10 amperes, 1% accuracy)
. Control switch for manual or automatic reset
. Ground fault contacts (1-NO/1-NC) for customer use
. Shorting terminal block for ground current CT
. Adjustable pulsing timer (0-10 seconds)
. Tapped resistors (across neutral forming transformer secondary, limiting primary current to 3-6 amperes)
. 3-position selector switch (normal, pulse, test)
. Indicating lights
Red (ground fault)
Green (normal)
White (pulse)
Components and Connections
Phase and neutral terminals shall accept #4 AWG to 500 kcmil wire. Ground terminals shall accept wire sizes from #8 AWG to 500 kcmil. Ground bus shall be 1/4-inch x 2-inch copper. #4 AWG wire shall be used for all internal connections from the neutral point to ground. Control connections shall be a minimum of #14 gauge. All control wire insulation shall be type SIS. All control wiring shall be labeled at each end. Wiring within the resistor assembly shall be rated for 200°C service.

Structure
The unit shall be free-standing and house the resistor bank within an isolated section of the structure. Access to the resistor shall be via a bolted-on cover. The rear cover shall be removable. The structure shall provide top and bottom cable entry points. Lifting angles shall be provided to facilitate the installation of the unit. The structure shall be suitable for moving on rollers and shall be skidded for shipment in a manner suitable for handling by a forklift. All steel parts (except for plated parts) shall be thoroughly cleaned and phosphatized prior to the application of the light gray ANSI No. 61 finish. A pocket is required on the inside of the control compartment door to store drawings and manuals.

Factory Assembly and Tests
The system shall be completely assembled, wired, and tested at the factory in accordance with NEMA and UL requirements. A certified production test report shall be shipped with the unit.